• 6000-Beam-IF
  • Fire Beam Interface

Fire Beam Interface

Part No. 6000/BEAM/IF
  • Protec Algo-Tec™ 6000 ProtocolLoop Powered
  • Monitored Zone Circuit
  • Integral Short Circuit Isolator
  • Standard Double Gang Back Box
  • Built in Local Power Supply (Nominal 24V)

Product Details

The Protec 6000/BEAM/IF is an interface unit which allows the 6000 series intelligent addressable loop to interface to conventional devices.

This is ideally suited to interface ancillary conventional devices such as beam detectors and linear heat detection with Protec intelligent addressable fire alarm systems. The 6000/BEAM/IF is loop powered and does not require an external power supply. The detection circuit end of line is selectable using the on-board DIL switch and can be programmed to resistive or capacitive as per the requirement of BS5839-1. The power circuit has a selectable 25mA or 50mA maximum current drive capability.

The interface has an inbuilt loop short circuit isolator fitted as standard.

Device ProtcolProtec Algo-Tec™ 6000
Environmental -10 to 50ºC (maximum 95% RH no condensation or icing)
Loop IsolatorYes
Loop Voltage18 to 28V peak loop
Number of Addresses1
Loop Quiescent Current0.8mA + detection circuit load ( 0.5mA max ) + resistive end of line load ( 3mA )
Loop Alarm Current7.5mA + detection circuit current + power circuit current
Power Circuit Voltage18 to 28V dc
Power Circuit Current LimitSelectable 25mA or 50mA ± 2mA
Detection Circuit EOL²Resistive – 8.2kΩ ±5% ¼W, Capacitive – 100μF ±20% in series with 22Ω ±5% ¼W
Detection Circuit Fire Value330Ω ±5% ¼W
Weight120g
IndicationsOn-board red indicating LED showing when the device is polled, or in the alarm state
Dimensions (mm) 147(W) x 87(H) x 15(D)