Addressable Fire Beam Detector
- Infra-Red Transmitter and Receiver
- Technician Friendly
- Simple Menu System
- Low Power Usage
- Automatic Beam Alignment
- Cost Effective
Product Details
The Protec 3000/FIREBEAM/70 is a conventional beam detector, which is compatible with the Protec 3000 range. The 3000/FIREBEAM70 Reflective Optical Beam Smoke Detector includes a motorised head unit containing an infrared transmitter and receiver, a ground-level controller and prism reflector.
The unit uses a 24V infrared transmitter to fire an infrared beam to a prism reflector, the returned beam is analysed for smoke contamination and registers a fire condition at a preprogrammed level.
The beam head incorporates microprocessor-controlled motors that intelligently maintain alignment with the reflector. When commissioned the head accurately aligns itself. In operation, the motorised head will re-align should there be building movement, a problem with new build settlement or environmental change. The unit’s unique ability to self-align means that high-level re-adjustment is no longer required; saving time, disruption and cost, all whilst delivering outstanding reliability that reduces troublesome false alarms.
The supplied controller unit is used to make operational adjustments. The uncomplicated menu system, presented on the controller’s LCD screen, helps simplify maintenance. All adjustments can be made at ground level, including a test procedure and full diagnostics.
The standard unit covers a range of 7 to 70 metres. To increase the beam’s range, additional reflectors can be added. Two kits are available; FIREBEAM70/140KIT for a range of 70 to 140 metres, and FIREBEAM140/160KIT for a range of 140 to 160 metres.
Benefiting from IP65 rated enclosures, on both the motorised head and the controller unit, the beam detector is suitable for hostile environments such as the wash down areas in food processing halls.
Addressable Option
![]() | The beam can be converted to a loop powered addressable device, by connecting it to the Protec 6000 Beam Interface Unit. |
Construction | Housing: white high heat abs UL94 HB |
Ingress Protection | IP65 |
Environment | -10ºC to 55ºC (10 to 95% R.H. non condensing) |
Weight | Approx: Head 1.1Kg / Controller 0.55Kg |
Dimensions (mm) | Beam Head – 155(W) x 180(H) x 137(D) Controller – 120(W) x 185(H) x 62(D) |
Time to Fault | Adjustable between 2s to 60s |
Time to Fire | Adjustable between 2s to 30s |
Sensitivity | Fully adjustable between 25% to 50% |
Supply Voltage | 12V dc to 24Vdc +25% -15% |
Quiescent Current | 3.5mA |
Alarm Current | 3.5mA |
Aligning Current | 3.5mA |
Fault/Fire Relay Contact Rating | 2A @ 30Vdc |
Relevant Standard | EN54 Part 12 |