Sigma XT+ 4 Multi Area Extinguishant Control Panel
- 2, 4 or 8 detection zones
- 1 to 4 extinguishant areas
- Dual extinguishant outputs for each area (configurable as Main/Reserve)
- First and second stage sounder outputs for each area
- First and second stage volt free changeover contacts for each area
- Released volt free contact per area
- Fault volt free contact per area
- Programmable extinguishant delays
- Programmable output duration
- Approved to EN12094-1, EN54-2 and EN54-4
Product Details
Sigma XT+ control panels are multi-area extinguishant control panels complying with EN12094-1, EN54-2 and EN54-4. Up to 8 zones of conventional detection with up to 4 extinguishant areas are available.
Stand alone extinguishant control units are also available with 2 monitored inputs to receive initiating signals from remote fire detection control panels or addressable modules.
Each extinguishant area has a comprehensive set of inputs and outputs and is configurable via a simple programming interface. All extinguishant areas may have up to 7, serially connected Sigma Si status indication and control units or ancillary relay boards connected via a simple 4 core cable.
The versatility of the control panel can be enhanced further by the fitting of up to 7 Sigma CP Ancillary boards (K580) or Sigma CP Sounder boards (K461) to the RS485 serial bus.
For compatible status units click here.
Key Features continued from above…
- Extract fan control
- Countdown indicator shows time until release in seconds
- Mode select and manual release controls per area
- Monitored remote manual release input
- Monitored remote Hold input
- Monitored remote Mode select (door interlock) input
- Monitored remote Released pressure switch input
- Monitored remote Low Pressure switch input
- Monitored Abort input
- Serial connection for Sigma Si status units and ancillary boards
| Construction | 1.2mm mild sheet steel |
| IP Rating | IP30 |
| Finish | Epoxy powder coated |
| Colour – lid & box | BS 00 A 05 grey – fine texture |
| Colour – controls plate & lables | RAL 7047 light grey – sation |
| Weight | 8kg (standard panel) |
| Mains supply | 230V AC, 50HZ + 10% – 15% (100 Watts maximum) |
| Mains supply fuse | 1.6 Amp (F1.6A L250V) |
| Power supply rating (1 & 2 area units) | 3 Amps total including battery charge 28V +/- 2V |
| Power supply rating (3 & 4 area units) | 5.25 Amps including battery charge 28V +/- 2V |
| Maximum ripple current | 200 millivolts |
| Battery charge voltage | 27.6VDC nominal (temperature compensated) |
| Battery charge current | 0.7A maximum |
| Battery fuse | 20mm, 3.15A glass |
| Current draw in mains fail condition | 54 milliamps per module |
| Max. current draw from betteries | 3A or 4A (Model dependant) |
| Sigma XT+ module Aux 24V output | Fused at 500mA with electronic fuse -1 per extinguishant area |
| Sigma CP Aux 24V output | Fused at 2.5A – not available to user |
| 1st and 2nd stage Sounder outputs | 21 to 28V DC Fused at 1A with electronic fuse |
| Fault relay contact rating | 5 to 30VDC 1A Amp maximum for each |
| Fire relay contact rating | 5 to 30VDC 1A Amp maximum for each |
| Local fire relay contact rating | 5 to 30VDC 1A Amp maximum for each |
| Fire stage contact rating | 5 to 30VDC 1A Amp maximum for each |
| Second stage contact rating | 5 to 30VDC 1A Amp maximum for each |
| Extract contact rating | 5 to 30VDC 1A Amp maximum for each |
| Zone quiescent current | 0mA minimum, 2mA maximum |
| Terminal capacity | 0.5mm² to 2.5mm² solid or stranded wire |
| Number of detectors per zone | Dependent on type – typically 20 |
| Number of sounders per circuit | Dependent on type and current consumption – typically 20+ |
| Detection circuit end of line | 6K8 +/- 5% ½ Watt resistor |
| Monitored input end of line | 6K8 +- 5% ½ Watt resistor |
| Sounder circuit end of line | 10K +/- 5% ¼ Watt resistor |
| Extinguishant output end of line | 1N4004 Diode |
| No. of detection circuits | Two to eight. 21 to 28V DC |
| No. of sounder circuits | Dependent on model 21 to 28V DC |
| Extinguishant release output | 21 to 28V DC. Fused at 1 Amp |
| Extinguishant release delay | Adjustable 0 to 60 seconds (+/- 10%) |
| Extinguishant release duration | Adjustable 60 to 300 seconds |
| SIL, AL, FLT, RST inputs | Switched -ve, min resistance 0ohms, max resistance 100 Ohms |
| Zone normal threshold (Allowable EOL) | 10K ohm to 2K ohm |
| Detector alarm threshold | 1K ohm to 390 ohms |
| Call point alarm threshold | 370 ohms to 150 ohms |
| Short circuit threshold | 130 ohms to 0 ohms |
| Head removal condition | 15.5 to 17.5 volts |
| Cabling | FP200 or equivalent (max capacitance 1uF max inductance 1 mH) |
| Monitored inputs normal threshold (Allowable EOL) | 10K ohm to 2K ohm |
| Monitored inputs alarm threshold | 2K ohms to 150 ohms +/- 5% |
| Monitored inputs Short circuit threshold | 140 ohms to 0 ohms +/- 5% |
| Status unit/Ancillary board connection | Two wired RS485 connection (EIA-485 specification) |
| Status unit power output | 21 to 28V DC. Fused at 500mA with electronic fuse |
| Dimensions (mm) | 385(W) x 520(H) x 110(D) 385(W) x 700(H) x 145(D) |
Technical documents such as Manuals, Software downloads, BIM families, and more are available via our Client / Support Portal. To access, please Sign up or Login to your account.
Sign up or login to your accountRelated Products


- Sigma Extinguishant Status IndicatorsView Product
- Sigma XT Extinguishant Control PanelView Product
- 3000PLUS Optical Heat DetectorView Product
- 3000PLUS 56°C Fast Response Heat DetectorView Product
- 3000 Red Wall Mounted SounderView Product
- Fire Alarm Bell 6” EN54-3 ApprovedView Product
- Detector Remote Indicator UnitView Product