EVX-OSA - Emergency Telephone Type A Outstation
- Compact design
- Ruggedised handset
- High volume ringer
- Status LED
- 20mm cable Gland knock-out
- Telecoil for hearing-impaired users
- Full duplex operation
- Fully compliant to BS5839-9:2011
- Magnetic push catch
- Stainless steel as standard
- Flush bezel available
Product Details
An EVCS is a fixed, secure, bi-directional, full duplex voice communication system to assist firefighters during emergencies in high-rise buildings or large sites where radio communication cannot be guaranteed to work due to interference from the fire corona.
BS 5839-9:2021 covers the design, installation and operation of fire telephones and disabled refuge systems in buildings, and where both systems are fitted to a building, the standard specifies these should form a single system.
The EVX-OSA is a Type A EVCS outstation compatible with the EVX standalone and network systems.
The outstation is supplied in a brushed stainless finish with a high contrast red screen print with a rugged red telephone handset behind the push door.
A stainless steel bezel is available to allow the outstation to be flushed into a wall reducing the need to stock flush and surface variants.
Suitability
The EVX-OSA is a Type A outstation as defined in BS 5839-9:2021, and can be used as a fire telephone or a disabled refuge call point.
The EVX outstations are designed for use by multi-disability users, having high contrast signage in line with RNIB guidelines and an induction loop coil (to BSEN60118-4) in the handset.
Type A outstations are mainly used by building management, fire wardens and firefighters. They should be located as described in BS9999 and Building Regulations Approved Document B, these locations should have a low background noise otherwise, you may have to consider acoustic hoods.
Mounting The Outstation
The outstation should be mounted at a height of 1300 to 1400mm from to the centre line of the outstation to the floor to comply with the requirements of Building Regulations Document M (Access for the Disabled).
When flush mounting a cut out of 305mm by 155mm is recommended, the bezel slides over the box and is fixed on the wall using a suitable sealant or mastic If the outstation is to also to be used as a refuge point, suitable space must be allowed so the system can be used by a parked wheelchair.
Physical
Dimensions (mm) | Surface | Bezel | Cutout |
Height | 300 | 350 | 305 |
Width | 150 | 200 | 155 |
Depth | 95 | 1 | 85 |
Weight | 1400kg |
Material | Stainless Steel |
Finish | Brushed |
Outstation Cables
Type | Enhanced Fire Resistant |
Cores | 2×2 core 1.5mm Screened |
Distance | 500m |
Standards Compliance
EMC | EN55103-1,EN55103-2 |
LVD | EN60950 |
Product Family | BS 5839-pt9:2021, BS9999, BS60118-4 |
Technical documents such as Manuals, Software downloads, BIM families, and more are available via our Client / Support Portal. To access, please Sign up or Login to your account.
Sign up or login to your accountRelated Products
- EVX-IPA – IP66 Weatherproof Type A Fire TelephoneView Product
- EVX-OSA – Emergency Telephone Type A OutstationView Product
- EVX-ILB – Type B Refuge Point with Integral Induction LoopView Product
- EVX-IPB2 – IP66 Weatherproof Type B Refuge PointView Product
- EVX-OSB-G Refuge Alarm Type B OutstationView Product
- EVX-RAP – Remote Alarm PanelView Product
- EVX-ACA – Assist Call WC Alarm KitView Product
- Roaming Handset and Jack PlateView Product