• 6000 Local Control Module

6000 Local Control Module

Part No. 6000/LCM
  • Loop Powered Single Zone Fire Alarm
  • Reduced Incidence of False Alarms in Houses in Multiple Occupation
  • Local ‘Mute’ facility to Silence Unwanted Alarms
  • Local‘Disable’ Facility to Isolate Local Detectors and Sounders
  • Simple One Button Operation
  • Fully Monitored
  • Low Current
  • Integral Short Circuit Isolator
  • Protec Algo-TecTM 6000 Protocol
  • Approved to EN54 Part 17 & 18

Product Details

The Protec Algo-Tec™ 6000 Local Control Module has been designed to allow easy integration of Protec Addressable Fire Detection systems into Houses in Multiple Occupancy and offers novel features to reduce false and nuisance alarms.

The unit effectively operates as a stand alone fire alarm control panel monitoring detectors and driving sounders in a zone. An automatic detector activation on the zone instigates a search timer to allow the cause of the alarm to be investigated, and dealt with locally, prior to signalling a full alarm to the building fire alarm system. The unit is loop powered and reports its status back to the master panel at regular intervals.

Operation

The device monitors the detection zone for activations, if one occurs the following decisions are taken.

  • If the activation is due to an MCP the device will immediately signal a fire condition to the host panel. This will then activate the unit and the local sounders will sound. The Local alarm LED on the unit will be illuminated.
  • If the activation is due to an automaticdevice being triggered, a ‘search’ time of one minute will be started before the system is put into alarm.

 

If the mute button is pressed before the search time expires the fire signal to the host panel is delayed by up to 2 minutes. If the zone returns to normal within this time no further action is taken.

If the mute button is pressed prior to an activation an ‘isolated’ period of 15 minutes is instigated. If the mute button is pressed again during the ‘isolated’ period the device returns to normal.

An internal buzzer sounds 15 seconds prior to either the muted or the isolated period expiring.

If the mute button is pressed during the 15 second expiry period the original time-out of 2 or 15 minutes is re-set.

If the master panel has a fire activation the device can be programmed to activate the sounder outputs, this overrides any muted, or isolated state.

Protocol ProtecAlgo-Tec™ 6000
Number of Addresses1
Loop Voltage Range18 to 28V
Loop PoweredYes
Loop Standby Load0.7mA quiescent + detector zone load (500μA max) + (3mA if resistive EOL used)
Loop Alarm Load (Max)5mA + detector zone load (12mA max) + sounder load (50mA max)
Sounders SupportedProtec 3000 or 3000PLUS low current electronic sounders
Sounder CurrentCurrent limit of 25mA or 50mA (switch selectable)
End of Line10kΩ 1/4W ± 5%
Cable Type2 core screened. 200 metres maximum length
Manual Call PointMust be fitted with 330ΩΩor 180Ω resistor
Detectors SupportedProtec 3000 and 3000PLUS
Short Circuit Current12mA maximum
Quiescent Current500μA maximum
Max Number of Detectors10
End Of Line Capacitive(100μF in series with 22Ω) or resistive (8.2kΩ 1/4W ± 5%)
Cable Type2 core screened. 200 metres maximum length
Environment0 to 50 (85% RH non condensing)
Ingress ProtectionIP21
Weight110g (no backbox)
Product ApprovalBSI No: KM589455
CoCP No: 2797-CPR-58945
DoP No: PFD-CPR-0064
Relevant Standard: EN54 Part 17 & 18

Technical documents such as Manuals, Software downloads, BIM families, and more are available via our Client / Support Portal. To access, please Sign up or Login to your account.

Contact our sales team today
Product
Acceptance *
Marketing