• 6000-APZA-and-6000-LPZA
  • Single Channel Ancillary Powered Zone Alarm Interface

Single Channel Ancillary Powered Zone Alarm Interface

Part No. 6000/APZA
  • Easy to Use
  • Reduce Installation Cost
  • Simple Expansion Using Existing Wiring
  • FAST™ Addressing
  • Integral Short Circuit Isolator
  • Auxiliary 24V dc Powered
  • Protec Conventional Detector and Call Point Zone
  • Built in Sounder Circuit Monitored for Open / Short Circuit Faults

Product Details

The Protec 6000/APZA is a zone alarm interface which allows the 6000 series intelligent addressable loop to interface to a zone of conventional devices and a conventional sounder circuit.

This interface is ideally suited for small conventional fire detection to be fully integrated with Protec Intelligent addressable systems. The 6000/APZA is powered using an external EN54 Part 4 power supply. It can support up to 10 Protec conventional (3000PLUS) detectors.

The zone end of line is selectable using the on board DIL switch and can be programmed to resistive or capacitive as per the requirement of BS5939-1. The sounder circuit is monitored for open and short circuit faults and has 1A current drive capability.

The interface has an inbuilt loop short circuit isolator fitted as standard.

Loop ProtocolProtec Algo-tec 6000™
Loop IsolatorYes
Loop Voltage18 to 28V peak loop
Number of Addresses1
24V Auxiliary Voltage18 to 28V dc
Environment-10 to 50°C (maximum 95% RH no condensation or icing)
Loop Quiescent Current0.6mA
Loop Alarm Current0.6mA
Auxiliary 24V Current0.6mA Quiescent + detector load ( 13mA max ) + resistive end of line load ( 3mA )
7.5mA Alarm, plus zone circuit current and sounder circuit current
Zone Circuit EOL²Resistive – 8.2Ω ±5% ¼W Capacitive – 100µF ±20% in series with 22Ω ±5% ¼W
Manual Call PointMust be fitted with a 330Ω or 180Ω series resistor
Detectors SupportedProtec 3000 and 3000PLUS
Sounders SupportedProtec 3000 series
Sounder Circuit EOL²10kΩ ±5% ¼W
Sounder Circuit Current1A
Weight120g
IndicationsOn-board red indicating LED showing when the device is polled, or in the alarm state
Product ApprovalBSI Kitemark No: KM589455
CoCP No: 0086-CPR-589456
DoP No: PFD-CPR-0059
Relevant Standard: EN54-17 & 18
CE Marked

Technical documents such as Manuals, Software downloads, BIM families, and more are available via our Client / Support Portal. To access, please Sign up or Login to your account.

Contact our sales team today
Product
Acceptance *
Marketing