• 6000-MICCO
  • Single Channel Interface - 6000/MICCO

Single Channel Interface - 6000/MICCO

Part No. 6000/MICCO
  • Protec Algo-Tec™ 6000 Protocol
  • Loop Powered
  • Monitored Input Interface
  • Clean Contact Output Interface
  • Integral Short Circuit Isolator

Product Details

Our single channel interface (6000/MICCO) is a loop-powered fault-monitored input and a volt-free clean contact output interface. An on-board isolator protects against loop short circuits on incoming or outgoing loop connections.

Protec advanced addressable fire alarm systems are equipped with a wide range of interfaces that can effortlessly and efficiently integrate third-party systems. Our cutting edge 6000PLUS protocol is used for comprehensive system monitoring, ensuring that in the event of an emergency, third-party systems such as gas, plant machinery, lifts, Automatic Opening Vents (AOV’s), etc., are promptly activated or shut down to minimise damage and ensure the safety of the building and its occupants.

To make the commissioning process simple, we have incorporated our FAST™ commissioning method and equipped the interface range with an inbuilt loop short circuit isolator to enhance reliability and safety. Our fire alarm system continuously monitors our interfaces to ensure maximum protection for the building and its occupants.

 

Product Code6000/MICCO
Environment-10°C to +50°C (95% R.H. non condensing)
Ingress ProtectionIP20
Weight109g
Din Rail MountedNo
Inputs1 x Monitored Input
Outputs1 x Clean Contact Output
IsolatorYes, on board (consult Protec DEL2110 for details)
Compatible Panels6500, 6100, 6400, 6300
Number of Loop Addresses Used1
Loop Alarm Current (Average)2.2 mA
Loop Alarm Current (Peak)5 mA
Loop Protocol6000/6000PLUS
Loop PoweredYes
Loop Voltage Range16 V dc – 28 V dc peak loop
Loop Quiescent Current (24V Loop Peak)0.55 mA
Zone Quiescent Currentn/a
Zone Reset Timen/a
Max Number of Detectorsn/a
Detectors Supportedn/a
Sounders Supportedn/a
Clean Contact Output DetailsSingle pole changeover rated for 8 A at maximum 30 V dc non inductive
Dimensions (mm)147.3(W) x 86.7(H) x 10(D)
Technical DocumentationDEL2109
Standards / ApprovalsEN 54-17, EN 54-18

UKCA

CE

Technical documents such as Manuals, Software downloads, BIM families, and more are available via our Client / Support Portal. To access, please Sign up or Login to your account.

Contact our sales team today
Product
Acceptance *
Marketing