Our single channel interface (6000/MICCO) is a loop-powered fault-monitored input and a volt-free clean contact output interface. An on-board isolator protects against loop short circuits on incoming or outgoing loop connections.
Protec advanced addressable fire alarm systems are equipped with a wide range of interfaces that can effortlessly and efficiently integrate third-party systems. Our cutting edge 6000PLUS protocol is used for comprehensive system monitoring, ensuring that in the event of an emergency, third-party systems such as gas, plant machinery, lifts, Automatic Opening Vents (AOV’s), etc., are promptly activated or shut down to minimise damage and ensure the safety of the building and its occupants.
To make the commissioning process simple, we have incorporated our FAST™ commissioning method and equipped the interface range with an inbuilt loop short circuit isolator to enhance reliability and safety. Our fire alarm system continuously monitors our interfaces to ensure maximum protection for the building and its occupants.
| Product Code | 6000/MICCO |
| Environment | -10°C to +50°C (95% R.H. non condensing) |
| Ingress Protection | IP20 |
| Weight | 109g |
| Din Rail Mounted | No |
| Inputs | 1 x Monitored Input |
| Outputs | 1 x Clean Contact Output |
| Isolator | Yes, on board (consult Protec DEL2110 for details) |
| Compatible Panels | 6500, 6100, 6400, 6300 |
| Number of Loop Addresses Used | 1 |
| Loop Alarm Current (Average) | 2.2 mA |
| Loop Alarm Current (Peak) | 5 mA |
| Loop Protocol | 6000/6000PLUS |
| Loop Powered | Yes |
| Loop Voltage Range | 16 V dc – 28 V dc peak loop |
| Loop Quiescent Current (24V Loop Peak) | 0.55 mA |
| Zone Quiescent Current | n/a |
| Zone Reset Time | n/a |
| Max Number of Detectors | n/a |
| Detectors Supported | n/a |
| Sounders Supported | n/a |
| Clean Contact Output Details | Single pole changeover rated for 8 A at maximum 30 V dc non inductive |
| Dimensions (mm) | 147.3(W) x 86.7(H) x 10(D) |
| Technical Documentation | DEL2109 |
| Standards / Approvals | EN 54-17, EN 54-18 UKCA CE |
Technical documents such as Manuals, Software downloads, BIM families, and more are available via our Client / Support Portal. To access, please Sign up or Login to your account.
Sign up or login to your accountRelated Products


- Interface Back BoxView Product
- Single Channel Auxiliary Powered Zone Alarm InterfaceView Product
- Single Channel Loop Powered Zone Alarm InterfaceView Product
- 2 Channel Ancillary Powered Zone Alarm InterfaceView Product
- 2 Channel Input/Output InterfaceView Product
- 2 Channel Loop Powered Zone Alarm InterfaceView Product
- 6000 Local Control ModuleView Product