The 6000PLUS Heat with Sounder Visual Alarm Device (6000PLUS/HT/SVAD) is an Interactive, fast and reliable heat detector using a low thermal mass thermistor for rapid response to rising temperatures. Intelligent Protec Algo‑Tec™ 6000PLUS algorithms ensure accurate decision‑making and reduced false alarms.
Ideal for areas where smoke detection is unsuitable, including:
- Boiler rooms
- Commercial kitchens
- Laundries
- Ventilated or high‑airflow spaces
The talking sounder is capable of delivering synchronised alert and evacuate messages around a building, removing any ambiguity, particularly for anyone unfamiliar with the building alert and evacuation strategy, enabling a more prompt and safe building evacuation.
Designed to support DDA requirements, the Visual Alarm Device (VAD) provides a clear visual warning for people with hearing impairments and in noisy environments The high-intensity, energy-efficient LED is centrally positioned VAD delivers reliable 360-degree visibility. Suitable for ceiling mounting, it achieves the required 0.4 lux illumination across the coverage area in compliance with EN54-23.
The device supports a maximum mounting height of 3m with a standard coverage diameter of 7.5m, and can be programmed on-site for 3m or 5m coverage at reduced power.
Tone Options
- Bell Tone: 800Hz
- Warble Tone: 990Hz(250ms), 730Hz(250ms)
- Continuous Tone: 990Hz
- Pulse Tone: 990Hz(500ms), Silence(500ms)
Tone Volume Options
The tone and volume are selectable at the control panel (measured at one metre):
- High: 85dB(A)
- Mid: 75dB(A)
- Low: 65dB(A)
BASE Options
- 6000PLUS/BASE – Low profile common mounting base
- 6000PLUS/FFBASE – Fast fixing semi recessed base
Note – base options above are included in the product approval.
| Product Code | 6000PLUS/HT/TSVAD |
| Environment | -10°C to +50°C (95% R.H. non condensing or icing) |
| Ingress Protection | IP21C |
| Weight | 109.46g |
| Loop Powered | Yes |
| Loop Standby Load | 0.55mA |
| Loop Alarm Load (Average) | 12.5mA |
| Loop Voltage | 18-28 V |
| Maximum Sounder Output Levels (Configured and Panel) | High 85dB (A), Mid 75 dB(A), Low 65dB(A) |
| VAD Flash Rate | 0.5Hz white flash |
| Mounting | Surface or recessed |
| Material | ABS to UL94-V0 flammability rating |
| Isolator | Yes |
| Cutout | n/a |
| Dimensions (mm) | 98.60Ø x 56.5(H) |
| Technical Documentation | DEL2130 |
| Standards / Approvals | EN 54-3, EN 54-5, EN 54-17, EN 54-23 UKCA CE |
- 6000PLUS/HT/TSVAD Datasheet
- 6000PLUS Sensor Brochure
- 6000PLUS Protocol Brochure
- Sensor Recognition Card
- Talking Sounder Messages
Technical documents such as Manuals, Software downloads, BIM families, and more are available via our Client / Support Portal. To access, please Sign up or Login to your account.
Sign up or login to your accountRelated Products


- 6000PLUS Heat SensorView Product
- 6000PLUS Heat Sensor inc. SounderView Product
- 6000PLUS Heat Sensor inc. Sounder & VADView Product
- 6000PLUS Optical Heat Sensor inc. Talking SounderView Product
- 6000PLUS Optical Heat Sensor inc. Talking Sounder & VADView Product
- 6000PLUS Optical Heat CO Sensor inc. Talking Sounder & VADView Product
- 6000PLUS Surface Mount Detector BaseView Product
- 6000PLUS Fast Fix Semi-Recessed Detector BaseView Product